Det-Tronics- Carrier Corporate

Ultra Flame Detection Releasing System Family (ULTRA FDRS)

The manufacturing of energetic materials and other specialized applications may require a flame detection and releasing system that is capable of a high-speed (not more than 500 milliseconds) or ultra-high-speed (not more than 100 milliseconds) response.

Three standardized, listed ULTRA FDRS systems are available to meet the needs of the small, medium and large ultra-high-speed system user. These models utilize the field-proven EQ3900 Approved Fire and Gas Releasing Cabinet solution.

Each model includes an appropriately sized cabinet housing an Eagle Quantum Premier® (EQP) Controller, one or more High-Speed Deluge Modules (HSDM), one or more Enhanced Discrete Input Output Modules (EDIO), physical disconnect switches and field wiring termination terminals.

Features and Technical Specifications

ULTRA FDRS 2400

  • Red painted (RAL 3020) steel enclosure, locking key handle door, fixed window, mounting feet, NEMA 4
  • 24”(H) x 20”(W) x 8”(D) (610mm x 508mm x 203mm)
  • Includes one (1) EQP Safety System Controller
  • Accommodates up to six (6) inputs from flame detectors (Class B)
  • Provides up to six (6) 24Vdc ultra-high-speed outputs (Class B)
  • Provides up to seven (7) non-high speed inputs or outputs
  • Lockable physical disconnect switches
  • Interposing terminals to accommodate field wiring
  • FM/CSA/IECEx and SIL 2 approved for indoor, non-hazardous areas
  • Allows compliance with NFPA 72® and NFPA 15 (Chapter 12)

ULTRA FDRS 3600

  • Red painted (RAL 3020) steel enclosure, locking key handle door, fixed window, mounting feet, NEMA 4
  • 36”(H) x 24”(W) x 8”(D) (914mm x 610mm x 203mm)
  • Includes one (1) EQP Safety System Controller
  • Accommodates up to eighteen (18) inputs from flame detectors (Class B)
  • Provides up to eighteen (18) 24VDC ultra-high-speed outputs (Class B)
  • Provides up to seven (7) non-high speed inputs or outputs
  • Lockable physical disconnect switches
  • Interposing terminals to accommodate field wiring
  • FM/CSA/IECEx and SIL 2 approved for indoor, non-hazardous areas
  • Allows compliance with NFPA 72® and NFPA 15 (Chapter 12)

ULTRA FDRS 4800

  • Red painted (RAL 3020) steel enclosure, locking key handle door, fixed window, mounting feet, NEMA 4
  • 48”(H) x 24”(W) x 10”(D)(1219mm x 610mm x 254mm)
  • Includes one (1) EQP Safety System Controller
  • Accommodates up to thirty (30) inputs from flame detectors (Class B)
  • Provides up to thirty (30) 24VDC ultra-high-speed outputs (Class B)
  • Provides up to seven (7) non-high speed inputs or outputs
  • Lockable physical disconnect switches
  • Interposing terminals to accommodate field wiring
  • FM/CSA/IECEx and SIL2 approved for indoor, non-hazardous areas
  • Allows compliance with NFPA 72® and NFPA 15 (Chapter 12)

ULTRA FDRS RIO    

This concept allows for installation of the ULTRA FDRS 2400, 3600, or 4800 in a given area while the ULTRA FDRS RIO is installed in a different area located physically closer to individual work areas. The ULTRA FDRS RIO Remote Input Output cabinet is ordered as needed in a quantity that is sized to the needs of the particular application.

Features and Technical Specifications

The ULTRA FDRS RIO Remote Input Output cabinet is ordered as needed in a quantity that is sized to the needs of the particular application.   

  • Red painted (RAL 3020) steel enclosure, locking key handle door, fixed window, mounting feet, NEMA 4
  • 36”(H) x 24”(W) x 8”(D) (914mm x 610mm x 203mm)
  • Accommodates up to eighteen (18) inputs from flame detectors (Class B)
  • Provides up to eighteen (18) 24VDC ultra-high-speed outputs (Class B)
  • Provides up to seven (7) non-high speed inputs or outputs
  • Lockable physical disconnect switches
  • Interposing terminals to accommodate field wiring
  • FM/CSA/IECEx and SIL2 approved for indoor, non-hazardous areas
  • Allows compliance with NFPA 72® and NFPA 15 (Chapter 12)

Standard Capacities

The following two tables summarize the specific capacities and dimensions of the different standard models. Other non-standard ULTRA FDRS options are available. These non-standard options may incur higher costs and longer lead times. 

System

Model

Flame Detector Inputs

Ultra-High-Speed Outputs

Non-High-Speed I/O

ULTRA FDRS 2400

6

6

7

ULTRA FDRS 3600

18

18

7

ULTRA FDRS 4800

30

30

7

ULTRA FDRS RIO

18

18

7

Hardware

Model

Enclosure Size

Door Window

EQP Controller Quantity

HSDM Quantity

EDIO Quantity Physical Disconnect Switch Quantity

ULTRA FDRS 2400

24" x 20" x 8"

610mm x 508mm x 203mm

Yes

1

1

2

ULTRA FDRS 3600

36" x 24" x 8"

914mm x 610mm x 203mm

Yes

1

3

6

ULTRA FDRS 4800

48" x 24" x 10"

1219mm x 610mm x 254mm

Yes

1

5

10

ULTRA FDRS RIO

36" x 24" x 8"

914mm x 610mm x 203mm

No

0

3

6

This site uses cookies. By continuing to use this site you are agreeing to use cookies. Find out more about our privacy policy.